To Continue our education of methods of fault detection :
Direction of Power flow :
must know the direction of the current , it's starting from generator and pass in
normal passing .
In case of back energy so the generator convert to motor and consider load on the
system because it take power .
Buchholze Relay :
It's fast mechanical device in its performance and founded in the transformer .
its contain of :
it has 2 buoy - the first buoy in the top and the second in the bottom , in case of
short circuit occur inside the transformer the oil boil and the gases go up until
the first buoy swings and its buoy for alarm .
in case of not dis-connect the transformer after the alarm , the gases increase
and the second buoy swings and occur trip and dis-connect the transformer .
Non Electrical quantities :
Temperature :
founded limit for oil temperature :
95 for alarm - 105 for Trip .
Founded limit for winding temperature :
105 for alarm 110 for trip
Pressure :
In case of delay the running of Buchholze Relay and Differential Relay the pressure
of oil increase and explodes the pressure relief .